The table below summarises the four decisive differences between the two methods, followed by the test-parameter differences that follow from them.

DC hipot test

VLF Testing (0.1 Hz)

AC-like. Capacitive and resistive grading both active; stress distribution reproduces service conditions at 0.1 Hz.

Purely resistive. Field is governed by conductivity, not permittivity, so grading layers and joint geometries are stressed differently from service.

Low. Polarity reverses every 5 s; injected charge recombines, and the cable is field-neutral after the test.

High. Charge trapped at voids, impurities, and interfaces; residual field superimposes on AC on re-energisation and can cause post-test failure.

Yes. Repeated field reversals break down tree-weakened insulation at or below test level; tan delta tip-up quantifies the degradation.

No. Water trees are effectively invisible under DC; degraded cable passes the test and fails in service.

Compact. Charging current is 500× lower than at 50 Hz, so a 30-80 kV set weighs about 30-90 kg and runs from a 230 V socket.

Compact set, but no diagnostic capability and no length advantage; requires a separate discharge and earthing procedure after the test.

2U₀ to 3U₀, 15-60 min (IEEE 400.2); 3U₀ for 15 min (HD 620 / VDE 0276-620).

Historically 2U₀ to 4U₀ for 5-15 min; now withdrawn for extruded cable by IEEE 400.2.

Tan delta, PD measurement, and leakage current monitoring on the same connection.

Leakage current only; no PD or dielectric-loss information.